Wiring for Damper Actuators and Control Valves
On/Off and Floating Point, Non-Spring Return, 24V
Blk 1 Common
Red 2 +
Wht 3 +
Blk 1 Common
Red 2 +
Wht 3 +
Floating Point
On/Off
Floating Point
On/Off – SPDT Switch
2 3 5
24 VAC Transformer
a open
a closed
Blk (1) Common
Red (2) +
Wht (3) +
a
Line
Volts
The indication of direction
is valid for switch position 1.
LMB(X)24-3...
NMB(X)24-3...
AMB(X)24-3...
GMB(X)24-3...
CMB24-3...
LRB(X)24-3...
ARB(X)24-3...
10
24 VAC Transformer
Blk (1) Common
Red (2) +
Wht (3) +
Line
Volts
The indication of direction
is valid for switch position 1.
2 3 5
10
24 VAC Transformer
TR24-3 (-T) US
Line
Volts
Note: TR24-3 (-T) US cannot
be wired in parallel with
any actuator.
5
TR24-3 (-T) US
24 VAC Transformer
Line
Volts
Note: TR24-3 (-T) US cannot
be wired in parallel with
any actuator.
Actuators: LMB24-3(-S) (-P5) (-P10) (-T) AMB24-3(-S) LMX24-3(-T) AMX24-3(-T) LRB24-3(-S) ARX24-3
TR24-3(-T) US
NMB24-3 GMB24-3… NMX24-3(-T) GMX24-3… ARB24-3(-S) LRX24-3
CMB24-3… ARB24-3-5 GRB24-3-5 GRB24-3-7 GMB24-3-X1 LRCB24-3(-S)
Actuators with plenum rated cable do not have
numbers on wires; use color codes instead.
Actuators with appliance cables are numbered.
The TR24-3-T US actuators are provided with
a numbered screw terminal strip instead of cable.
TR24-3 US actuators cannot be wired in parallel.
3
Actuators may also be powered by 24 VDC.
5
16
17
Meets cULus requirements without the need of an
electrical ground connection.
Equipment damage!
Actuators may be connected in parallel. Power
consumption and input impedance must be observed.
2
CAUTION
Indicates a potentially hazardous situation which, if not avoided,
may result in minor or moderate injury. It may also be used to
alert against unsafe practices.
Warnings and Cautions appear at appropriate sections throughout
this manual. Read these carefully.
Hazard Identification
INSTALLATION NOTES
APPLICATION NOTES
LMB(X)24-3...
NMB(X)24-3...
AMB(X)24-3...
GMB(X)24-3...
CMB24-3...
LRB(X)24-3...
ARB(X)24-3...
16 17
5
16 17
W332_11
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical
components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live electrical
components perform these tasks. Failure to follow all electrical
safety precautions when exposed to live electrical components
could result in death or serious injury.
Refer to page 26 for auxiliary switch (-S models) and -P5, -P10 potentiometer wiring.