800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN
18
N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc.
NVF24-MFT US
NVF24-MFT-E US
NVFD24-MFT US
NVFD24-MFT-E US
NV24-MFT US
NVD24-MFT US
Blk (1) Common
Red (2) + Hot
Wht (3)
Y
1
Input, 2 to 10V
Wht (5)
U Output, 2 to 10V
24 VAC Transformer
Control Signal
(+)
VDC/mA
(–)
Feedback Signal
(+)
2 to 10 VDC
(–)
Ω
500 Ω
Line
Volts
MFT Typical 2 to 10 VDC or 4 to 20 mA Wiring (diagram shown with
default position of S3.2: 3-way Off, 2-way On)
NVF24-MFT US
NVF24-MFT-E US
NVFD24-MFT US
NVFD24-MFT-E US
NV24-MFT US
NVD24-MFT US
Blk (1) – Common
Red (2) + Hot
Wht (3) Y
1
Input
Wht (5)
U Output,
2 to 10V
24 VAC Transformer
Requires diode
Feedback Signal
2 to 10 VDC
Line
Volts
Floating Point Control. (diagram shown with default position of
S3.2: 3-way Off, 2-way On.)
NVF24-MFT US
NVF24-MFT-E US
NVFD24-MFT US
NVFD24-MFT-E US
NV24-MFT US
NVD24-MFT US
Blk (1) – Common
Red (2) + Hot
Wht (3) Y Input
Wht (5) U Output
24 VAC Transformer
Feedback Signal
(+)
2 to 10 VDC
(–)
Line
Volts
Pulse Width Modulation Control Wiring (diagram shown with default
position of S3.2: 3-way Off, 2-way On)
Triac Source Floating Point
12
NVF24-MFT US
NVF24-MFT-E US
NVFD24-MFT US
NVFD24-MFT-E US
NV24-MFT US
NVD24-MFT US
Blk (1) Common
Red (2) + Hot
Wht (3)
Y
1
Input, 2 to 10V
Wht (5)
U Output, 2 to 10V
24 VAC Transformer (AC only)
Line
Volts
CCW CW
Hot
Controller
Position
Feedback
COM
A
B
CCW
CW
AB
1
CCW
CW
AB
1
Direction of rotation switch
SPRING RETURN ACTUATORS MODEL DESIGNATION
extending plunger (spring down)
NVFD24-E US
NVFD24-MFT-E US
NVF24-MFT-E US
retracting plunger (spring up)
NVFD24 US
NVFD24-MFT US
NVF24-MFT US
8
For triac sink the Common connection from the actuator
must be connected to the Hot connection of the controller.
Position feedback cannot be used with a triac sink controller.
The actuator internal common reference is not compatible.
10
12
12
12
12
Meets cULus requirements without the need of an
electrical ground connection.
Equipment damage!
Actuators may be connected in parallel. Power consumption
and input impedance must be observed.
2
8
2
CAUTION
Indicates a potentially hazardous situation which, if not avoided,
may result in minor or moderate injury. It may also be used to
alert against unsafe practices.
Warnings and Cautions appear at appropriate sections throughout
this manual. Read these carefully.
Hazard Identification
INSTALLATION NOTES
APPLICATION NOTES
Actuators: NVF24-MFT (-E) US NVFD24-MFT (-E) US NV24-MFT US NVD24-MFT US
2
2
2
IN4004 or IN4007 diode.
(IN4007 supplied, Belimo part number 40155)
Control signal may be pulsed from either the Hot (Source)
or Common (Sink) 24 VAC line.
Triac Sink Floating Point
12
NVF24-MFT US
NVF24-MFT-E US
NVFD24-MFT US
NVFD24-MFT-E US
NV24-MFT US
NVD24-MFT US
Blk (1) Common
Red (2) + Hot
Wht (3)
Y
1
Input, 2 to 10V
Wht (5)
U Output, 2 to 10V
24 VAC Transformer (AC only)
Line
Volts
Hot
Controller
COM
2
10
W607_11
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical
components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live electrical
components perform these tasks. Failure to follow all electrical
safety precautions when exposed to live electrical components
could result in death or serious injury.
Wiring for Control Valves
MFT, Spring and Non-Spring Return, 24V
Kommentare zu diesen Handbüchern