Wiring multiple...MFT actuators to single shaft and/or on
valves. All MFT actuators are wired in master-slave
configuration.
MFT actuator configurations should also co-ordinate with
each other. Meaning the master input = controllers output.
Master output = slave input. Slave output = controller input.
Controller
Output
Slave
Input
Slave
Feedback
Master
Feedback
0.1 to 25.5 sec 2 to 10 VDC 2 to 10 VDC 0 to 5 VDC
Equipment damage!
Actuators may be connected in parallel if not mechanically
mounted to the same shaft. Power consumption and input
impedance must be observed.
4
CAUTION
Indicates a potentially hazardous situation which, if not avoided,
may result in minor or moderate injury. It may also be used to
alert against unsafe practices.
Warnings and Cautions appear at appropriate sections throughout
this manual. Read these carefully.
Hazard Identification
Actuators with plenum rated cable do not have numbers on
wires; use color codes instead. Actuators with appliance
cables are numbered.
3
Actuators may also be powered by 24 VDC.
5
8
INSTALLATION NOTES
Control signal may be pulsed from either the Hot or
Common 24 VAC line.
Blk (1) Common
Red (2) + Hot
Wht (3) Y
Input
Org (5) U Output
CCW CW
Master
CCW CW
Slave
24 VAC Transformer (AC Only)
Line
Volts
Position
Feedback VDC
0 to 5 VDC
(–)
(+)
8
3
5
4
5
.1 to 25.5 sec
2 to 10 VDC
Blk (1) Common
Red (2) + Hot
Wht (3) Y
Input
Org (5) U Output
2 to 10 VDC
Pulse Width Modulation
Control Type: PWM
Example
W234_A_11
GMX(B)24-MFT 2
640 in-lb
Multiple Actuators Mounted to One Control Shaft
Model Max. Qty Per Shaft Torque Generated
EFB24-MFT(-S)
EFX24-MFT(-S)
3
810 in-lb
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical
components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live electrical
components perform these tasks. Failure to follow all electrical
safety precautions when exposed to live electrical components
could result in death or serious injury.
GKX(B)24-MFT 2
640 in-lb
AFB24-MFT(-S)
AFX24-MFT(-S)
3
432 in-lb